Braeburn

Braeburn 4030 Universal 7, 5-2 Day or Non-Programmable 2H / 1C with Dry Contact

Braeburn 4030 Universal 7, 5-2 Day or Non-Programmable 2H / 1C with Dry Contact

Dropship

SKU SKU:kpi105-4030

Regular price $74.51 USD
Regular price Sale price $74.51 USD
Sale Sold out
Shipping calculated at checkout.
View full details
  • 30-day returns
  • Fast shipping
  • Secure payments
  • Over 300,000 products
category: Sensors
install_guide: ["https://www.braeburnonline.com/sites/braeburn/files/products/manuals/4030%204235%20Installer.pdf"]
manual: https://www.braeburnonline.com/sites/braeburn/files/products/manuals/4030%204235%20User.pdf
manufacturer: Braeburn
mpn: 4030
subcategory: Thermostats
type: Room Thermostats
weight: .95 lbs.

Product Overview

Universal 7, 5-2 Day or Non-Programmable, 2H / 1C with Dry Contact

Features
  • 7 Day, 5-2 Day or Non-Programmable
  • Large Display with Adjustable Backlight
  • Auto or Manual Changeover
  • SmartLimit Temperature Limits
  • Indoor or Outdoor Remote Sensing*
  • SpeedSet Programming Mode
  • Hardwire or Battery Powered
  • User and Installer Lock Modes
  • Pre-Occupancy Purge Option
  • Auxiliary Heat Fossil Fuel Option
  • Programmable and Circulating Fan Modes
  • Adaptive Recovery Mode (ARM )
  • Temporary Override Limits
  • Compatible with 2 or 3 Wire Hydronic Zone Systems
  • Multi-Function Dry Contact Input for Occupancy Control, Condensate Monitoring or Door Switch Activation

Additional Information

Dimensions 4.25” x 5.12” x 1”
Electric Rating 24 Volt AC (18-30 Volt AC), 1 amp maximum load per terminal, 4 amp total maximum load (all terminals)
AC Power 18-30 Volt AC
DC Power 3.0 Volts DC, (2 “AA” Alkaline batteries included)
Compatibility Single stage gas, oil, electric or hydronic systems Single stage heat pumps with or without auxiliary heat 250mv – 750mv millivolt heating systems
Control Range 45° to 90° F (7° to 32° C)
Display Range 35° to 99° F (1.5° to 37° C)
Accuracy +/- 1° F (+/- .5° C)
Temperature Differential 0.5°, 1°, or 2° F (0.2°, 0.5°, or 1° C)
Storage Temperature 14° to 140° F (-10° to 60° C)
Operating Humidity 5% to 95% Relative Humidity
Terminations Rc, Rh, O/B/V3, Y1, W1/E, G, C, L, S1, S2, DRY1, DRY2