Product Overview
Mechanical Water Feeders/Low Water Cut-Offs
Product Features- For low pressure steam and hot water boilers larger than 5,000 sq. ft. (465m sq.) capacity with cold water feed
- Quick-change replaceable cartridge valve and strainer
- Comes with a No. 2 switch to add low water cut-off function
- Maximum water supply pressure 150 psi (10.5 lg/cm sq.)
- Maximum inlet water temperature 120 degrees F (49 degrees C)
- Maximum vessel pressure 35 psi (2.5 kg/cm sq.)
- Manual reset
- Float block
- Proportional feed action
Additional Information
ApplicationSteam BoilersHot Water Boilers
TypeFloat-Style
Max Pressure (PSI)150
Max Vessel Pressure35 psi
Reset TypeAutomatic
Max Inlet Water Temp (F)120°F
Width (Inches)9"
Height10.375"
Electrical Ratings (AFL)5.1 A @ 240 VAC10.2 A @ 120 VAC
Electrical Ratings (ALR)30.6 @ 240 VAC61.2 @ 120 Vac
Pilot Duty Rating125 VA
Size1"
Connection TypeThreaded
Switch#2