Suitable for pressure measurement in Oil Gas installations (onshore and offshore), power generation, including renewable energy facilities, wastewater locations and many other hazardous areas.
Additional Information
Input4/20 mA + HART, 2-wire / V
LCD DisplayAvailable with LCD display (standard) or without LCD display (optional)
Accuracy0.1% URL standard
Stability0.2% of URL for two years
Temperature RangesWorking/Media temperature: -25/95°C (with display -13/203°F), -40/185°C (without display -4/158°F), Ambient temperature: -40/60°C (with display -40/140°F), -40/115°C (without display -4/240°F), Storage temperature: -40/110°C (with display -40/85°F), -40/230°C (without display -40/446°F)
Working Humidity0-100% relative humidity
Pressure Connection1/2” NPT M or F, G1/2”, M20*1.5
Housing304SS, 316SS, Rugged die-cast aluminum housing (painted Blue)
Wetted Parts316 SS process connection, 316 L diaphragm
Response Time200ms
Turn On Time2 seconds (with minimum damping enabled)
Power Consumption 162.8 mW
Vibration Effect+/- 0.005% of URL per G to 200 Hz, in accordance to IEC60770-1:1999
Available Pressure UnitskPa, Mpa, bar, psi, mmHg, mmH2O, mH2O, inH2O, ftH2O, inHg, mHg, TORR, mbar, g/cm2, kg/cm2, Pa, ATM, m, cm, mm
Protection ClassEMC, reverse polarity protected
ApprovalATEX, II 2 G Ex db IIC T6 Gb, ATEX, II 1 G Ex ia IIC T1~T6 Ga, Intrinsically safe parameters: Ui
Protection ClassIP66
Weight5.95 lbs (2.7 kg)
Operational Life100 million cycles